User operation error status - 4, System service execution status – Yaskawa MP940 Reference Manual User Manual
Page 345

MotionSuite™ MP940 Machine Controller Reference Manual
System Errors
9-17
The latest data trace record number appears below.
User Operation Error Status - 4
Error
Code
Error Content
User
System Default
Integer/Real
Number
Operation
1000H
Index errors within drawing
—
Re-execute with i, j = 0
2000H
Index errors within function
—
Re-execute with i, ,j = 0
Integer
Operation
x060H
~
x077H
(x=1,2)
Integer-type System Functions
Index Error
—
Operation Hold and Output =
Input
The A register remains the
same
x06DH:PI
x06DH:PD
x06FH:PID
x070H:LAG
x071H:LLAG
x072H:FGN
x073H:IFGN
x074H:LAU
x075H:SLAU
x076H:FGN
x077H:IFGN
—
System Service Execution Status
Name
Register
Number
Reference
System Error Count
SW00090
—
System Error Codes
SW00091
—
Fault Occurrence Count
SW00092
—
Fault Recovery Count
SW00093
—
Reserved by System
SW00094 ~ SW00097 (Unused)
Existence of Data Trace Definition
SW00098
bit0 ~ 3 = Group1
Defined = 1; Undefined = 0
Data Trace Execution Status
SW00099
bit0 ~ 3 = Group 1
Trace Executing = 1; Trace Stopped = 0
Name
Register Number
Reference
Data Trace Group 1
SW00100
Latest Record Number