Troubleshooting

MotionSuite™ MP940 Machine Controller Reference Manual

10-8

A.10

A.10 is the overcurrent or heat sink overheat alarm display. The alarm output
appears below.

Note:

The

indicates the output transistor is ON; the x indicates the output transistor is OFF (alarm

state).

Status when Alarm Occurred

Note:

E ~ H may cause alarms in 1.5kW ~ 3kW servo amplifiers.

Alarm Output

Alarm Code Output

ALM Output

ALO1

ALO2

ALO3

x

x

x

Cause

Remedy

A

Wiring grounded between servo ampli-
fier and servo motor.

Check and correct the wiring.

B

Servo motor U, V, or W phase grounded. Replace servo motor.

C

Circuit board (1PEB) defective.
Power transistor defective.

Replace servo amplifier.

D

Current feedback circuit, power transis-
tor, DB circuit, or circuit board defective.

Replace servo amplifier.

E

The ambient temperature of the servo
amplifier exceeds 55ºC.

Lower the ambient temperature
to below 55ºC.

F

Poor airflow around heat sink.

Make the mounting, peripheral
space as per manual.

G

Fan stopped.

Replace servo amplifier.

H

Running above rated load.

Lighten load.

Alarm occurrs during

motor operation

A,B,D,E,

F,G,H

C, D

C

Alarm occurrs at power

ON

Alarm occurrs when servo

ON signal (S-ON) is ON