Position Control

MotionSuite™ MP940 Machine Controller Reference Manual

11-40

1. Method for Use as a Position Reference

1. Set the RUN command setting (bit 12 of OWC001) to ON.

2. In the position reference setting (OLC012), set a position buffer number

between 1 ~ 256 instead of the position reference.

By doing so, the data of the position buffer number designated in OLC012
will function as a position reference.

Position Monitor

The following parameters exist for position monitoring.

Motion Monitoring

Parameter Number

(register number)

Name

Content

ILC002

Machine Coordinate

a

Calculation

Position (CPOS).

Messages the calculated machine coordi-
nate position managed by the SVA mod-
ule.The position data messaged to this
parameter is the target position at each
scan. *1

ILC008

Machine Coordinate Feedback
Position (APOS)

Messages the machine ccordinate feedback
position.*2

ILC018

Machine Coordinate Command
Position (MPOS)

Messages the position output by the SVA
module to the outside and the machine
coordinate reference position.
This position data cannot be updated in the
machine lock state (no output to peripherals
in the machine lock state).
This is the same as ILC002 when the
machine lock function is not used.

ILC02E

Command Coordinate
Calculation Position (POS)

Significant when the axis selection is “infi-
nite length axis”.
In an infinite length axis, the target position
for each scan is messaged to the position
reference in this parameter.*3

Position Buffer

OLC012

Position Buffer Number

12345

1

OBC001C

OWC001

This value

becomes the

position reference