Sequence related parameters (continued) – Yaskawa MP940 Reference Manual User Manual

Page 289

Advertising
background image

MotionSuite™ MP940 Machine Controller Reference Manual

SGDH User Parameters

6-89

Pn509
Momentary Hold Time

ms
20 ~ 1000

When the power voltage to the servo
amplifier is momentarily turned OFF,
the servo amplifier detects this condi-
tion, and shuts off the servo.The 20ms
factory setting means that operation
continues as is if a momentary power
loss is 20ms or less. However, in the
following cases, this has nothing to do
with the setting of the Momentary Hold
Time, but is rather related to servo
alarms or control not possible states
(these are handled in the same way as
normal power OFF operations).
When the servo motor load is exces-
sive, and a low voltage alarm (A.41) is
generated in a momentary power loss;
when control becomes impossible
(handled in the same way as a normal
power OFF operation) during a
momentary loss of control power.
Momentary power loss detection
detects an ON/OFF state in the main
circuit power. The off state is ignored
and operation continues if the recovery
form OFF to ON is occurs within the
time set in user parameter Pn509.

20

Speed
Torque
Position

Sequence Related Parameters (Continued)

User

Parameter

Number

Digit

Position

Name

(setting

range)

Content

Default
Setting

Control

Mode

Source

Voltage

Occurence of

Momentary Power Loss

t OFF

Time

In (1)

In (2)

Servo ON

Servo ON

Servo OFF

(1) Pn509 Setting >

t OFF

(2) Pn509 Setting <

t OFF

Advertising