MotionSuite™ MP940 Machine Controller Reference Manual

External Positioning (EX_POSING)

11-59

1. Set initial fixed motion parameter and motion setting parameter values

to match the customer's machine.

2. Select the position control mode (PCON) (Bit 2 of OWC000).

3. Set the motion setting parameters used in external positioning

(EX_POSING).

4. Turn the RUN command (Bit 0 of OWC001) ON.

Set external positioning (EX_POSING = 2) in the motion commands
(OWC020).

a.

External Positioning Command Run Start

Speed

(%)

(100%)

0

Time

(t)

Fast Feed

Speed

Linear Acceleration

Time Constant

Linear Deceleration

Time Constant

Rated Speed

1. Fixed Motion Parameter Setting
Setting of initial motion setting parameters

2. Set Position Control Mode (PCON)

3. Set motion setting parameters

4. Turn Servo ON (RUN) ON

6. Start of positioning operation

Signifies system execution.

5. Motion Commands
Execute external positioning
(EX_POSING)

7. Moves for the external only positioning
run distance at latch signal input

POSCONP

Positioning Completion Range

Signifies user setting.

Latch Signal (External Positioning Signal)

External

Positioning

Run Distance

8. Positioning completion signal
(POSCOMP) is ON

9. Motion Command Release
(Executes (NOP (=0))

RUN

PCON

Motion
Command

(EX-POSING)