Yaskawa MP940 Reference Manual User Manual

Page 370

Advertising
background image

MotionSuite™ MP940 Machine Controller Reference Manual

Troubleshooting

10-17

A.7A

A.7A is the heat sink overheat alarm display. The alarm output appears
below.

Note: The indicates the output transistor is ON; the x indicates the output transistor is OFF

(alarm state).

Status when Alarm Occurred

Note: This alarm display occurs only in 30W ~ 1000W servo amplifiers.

Alarm Output

Alarm Code Output

ALM Output

ALO1

ALO2

ALO3

x

Cause

Remedy

A

The ambient temperature of the
servo amplifier exceeds 55ºC.

Lower the ambient temperature to
below 55ºC.

B

Poor airflow around heat sink.

Make the mounting, peripheral
space as per manual.

C

Fan stopped.

Replace servo amplifier.

D

Running above rated load.

Lighten load.

E

Servo amplifier defective.

Replace servo amplifier.

Alarm occurs only at power
ON

E

Alarm occurs during motor
operation

A, B, C, D

Advertising