C-phase pulse format, Dec1+zerosignal format – Yaskawa MP940 Reference Manual User Manual

Page 468

Advertising
background image

MotionSuite™ MP940 Machine Controller Reference Manual

Zero-point Return (ZRET)

11-71

1. Moves in a reverse direction at approach speed.

2. Decelerates at the upward transfer of the transition (deceleration LS)

signal.

3. Moves in a forward direction at approach speed.

4. After detecting the downward transfer of the transition pulse (decelera-

tion LS), the axis moves from the initial zero-point signal by the zero-
point return run distance at the upward transfer of the pulse transition,
stops, then assumes that position as the machine coordinate zero-point.

C-phase Pulse Format

Execute zero-point return in which only the zero-point signal (C-phase
pulse) following feed by linear accel/decel is used.

1. Moves at approach speed in the direction designated in the motion set-

ting servo parameter (OBC009).

2. Decelerates to creep speed after detection of the initial zero-point sig-

nal.

3. The axis will move from the initial zero-point signal by the zero-point

return run distance, stop, then assume that position as the machine
coordinate zero point.

DEC1+ZEROSignal Format

Executes zero-point return using the ZERO signal (DI signal) instead of
the C-phase pulse in the aforementioned “DEC1+C-phase Pulse Format”.

For details, see the aforementioned “DEC1+C-phase Pulse Format”.

Speed

Reference

0

Reverse Forward

Zero

Point

Creep Speed

Zero Point Signal

(C-phase pulse)

Time

1.

2.

3.

Zero Point

Return

Position

Zero Point Return Final

Run Distance