Torque related constants (continued) – Yaskawa MP940 Reference Manual User Manual

Page 280

Advertising
background image

SGDH User Parameters

MotionSuite™ MP940 Machine Controller Reference Manual

6-80

Pn405
Reverse External Torque Limit

P-CL at ON

Applies the torque

OBC0013 = 1

limit to the forward
direction

P-CL at OFF
OBC0013 = 0

Does not apply the
torque limit to the
forward direction.

N-CL at ON

Applies the torque

OBC0014 = 1

limit to the reverse
direction

N-CL at OFF

Does not apply the

OBC0014 = 0

torque limit to the
reverse direction.
Normal run.

Limit
Value:
Pn404

Limit
Value:
Pn405

The following signal is output during torque
limit application.

CLT=IBC001B

(Bit 11 of motion monitor parameter Servo
Drive Status)
Monitor Mode
Un005: No. 6, No. 7(for factory settings)
Un006: According to output signal assign-
ment conditions.
Application Example
Pushing Stop Operation
Robot Work Protection

Pn406
Emergency Stop Torque

%
0 ~ 800

Sets the stopping torque at overtravel (for-
ward prohibit input, reverse prohibit input).
Enabled when 1 or 2 is set in Stopping
Method at Overtravel (Pn001.1).
The setting unit is in % of rated torque.

For details on overtravel, see Pn001.1.

800

Speed
Position

Torque Related Constants (Continued)

User

Parameter

Number

Digit

Position

Name

(setting

range)

Content

Default

Setting

Control

Mode

Coast to Stop

DB Stop

Decel Stop

Maximum

Emergency Stop

Torque Setting

Forward Prohibit

Input

P-OT(CN1-42)

Reverse Prohibit

Input

OT(CN1-43)

Pn001.1

Pn406