Servo Amplifier Maintenance/Inspection

MotionSuite™ MP940 Machine Controller Reference Manual

10-2

Servo Amplifier Inspection

The inspection of the servo amplifier is outlined in the table below. Although
daily inspection is not necessary, carry out an inspection at least once a year.

Part Replacement Schedule

The following parts are subject to wear and mechnical deterioration over
time. To avoid failure, replace these parts at the frequency indicated.

If the servo amplifier has already been overhauled at Yaskawa, its user
parameters are set back to the standard setting at shipment. Always check the
user parameters before operating the motor.

Periodic parts inspection guidelines appear below.

Operating Conditions

Ambient Temperature: annual average 30ºC

Load Factor: 80% maximum

Operation Rate: 20 hours/day maximum

Inspection Items

Frequency

Procedure

Remedy

Clean unit interior and
circuit boards

Yearly

Check for dust, dirt, and oil
on the surfaces.

Clean with compressed air.

Loose screws

Yearly

Check for loose terminal
block and connector screws.

Tighten any loose screws.

Defective parts in unit
or on circuit boards

Yearly

Check for damage, discolor-
ation, or discontinuities due
to heating

Contact your Yaskawa rep-
resentative.

Part

Standard

Replacement

Period

Replacement Method

Cooling fan

4 to 5 years

Replace with new part.

Smoothing Capacitor

7 to 8 years

Test. Replace with new part if necessary.

Relays

Test. Replace if necessary.

Fuse

10 years

Replace with new part.

Aluminium Electrolytic Capacitor
on Circuit Board

5 years

Test. Replace with new circuit board if necessary.