Troubleshooting
MotionSuite™ MP940 Machine Controller Reference Manual
10-26
A.b2
A.b2 is the alarm display for the torque reference input read error alarm. The
alarm output appears below.
Note: The x indicates the output transistor is OFF (alarm state).
Status when Alarm Occurred
Alarm Output
Alarm Code Output
ALM Output
ALO1
ALO2
ALO3
x
x
x
x
Cause
Remedy
A
Part malfunctioned in reference
read-in unit (A/D converter, etc.).
Reset alarm and restart operation.
B
Part defective in reference read-in
unit (A/D converter, etc.).
Replace servo amplifier.
C
Circuit board (1PWB) defective.
Replace servo amplifier.
Alarm occurs at power ON
C
Alarm occurs during motor
operation
A,B