Troubleshooting
MotionSuite™ MP940 Machine Controller Reference Manual
10-36
A.F1
A.F1 is the power line open phase alarm display. The alarm output appears
below.
Note: The indicates the output transistor is ON; the x indicates the output transistor is OFF
(alarm state).
Status when Alarm Occurred
Note: Alarm A and B displays occur only in servo amplifiers of 500W or greater.
Alarm Output
Alarm Code Output
ALM Output
ALO1
ALO2
ALO3
x
x
x
Cause
Remedy
A
One phase (L1, L2, L3) of the
main circuit power supply is dis-
connected.
Check power supply.
Check wiring of the main circuit power supply.
Check MCCB, noise filter, magnetic contactor.
B
One phase line has low voltage.
Check power supply.
C
Servo amplifier defective.
Replace servo amplifier.
Alarm occurs at brake power
only ON
C
Alarm occurs at main power
ON
A, B