Troubleshooting

MotionSuite™ MP940 Machine Controller Reference Manual

10-32

A.d0

A.d0 is the alarm display for position deviation pulse overflow. The alarm
output appears below.

Note: The indicates the output transistor is ON; the x indicates the output transistor is OFF

(alarm state).

Status when Alarm Occurred

Alarm Output

Alarm Code Output

ALM Output

ALO1

ALO2

ALO3

x

x

Cause

Remedy

A

Mistaken servo motor wiring.

Check and correct the wiring.

B

Poor servo amplifier tuning.

Raise the speed loop gain (Pn100) and
position loop gain (Pn102).

C

Excessive motor load.

Reduce load torque and inertia. Other-
wise replace with larger capacity servo
motor.

D

Position reference pulse fre-
quency too high.

Slow-up or slow-down the reference
pulse frequency.
Install the smoothing function.
Review the electronic gear ratio.

E

Circuit board (1PWB) defective. Replace servo amplifier.

Alarm occurs at power ON

E

Alarm occurs during motor
operation

Overflow occurs at
high speed

A

Command pulse
enters, but no
feedback pulse is
returned

E

Operation is normal,

but long commands
result in overflow

B, C, D