Troubleshooting Outline

MotionSuite™ MP940 Machine Controller Reference Manual

9-4

Content of LED Display

The display content and countermeasure methods for the LEDs displaying
the MP940 operation status and error content are shown below.

Note: In the display light LED ×: OFF;

:ON; §:Flash; —:Undefined

Type

Display Light Name

Display Content

Countermeasure

RDY RUN

ALM

BAT

Nor-
mal

×

×

×

Hardware Reset State

The CPU normally starts within 1 second. If
this state continues, there is a software error/
hardware fault. Execute system error coun-
termeasures.

×

×

×

×

Initial Execution

×

×

×

User Program Stopped
(online stop mode)

When a STOP operation is executed by

MotionWorks

TM

. This state results when the

RUN switch is turned OFF.

×

×

User Program Executing
Normally

This state results during normal execution.

Error

×

×

Major Fault Generation

×

×

Program Memory
Initialization Complete
Scan Time Setting
Error

Execute the program memory clear operation

in the MotionWorks

TM

system definition

screen. A hardware failure is suspected if the
system does not recover.

×

×

§

×

Hardware Error
Number of Flashes
2: RAM Diagnostic Error
3: ROM Diagnostic Error
4: CPU Function Diag-
nostic Error
5: FPU Function Diag-
nostic Error

Hardware fault. Execute system error counter-
measures.

Warn-
ing

Battery Alarm

Replace the battery.

§

Operation Error

I/O Error

Invalid Assignment Error —

Report to system register
(no LED display)

MotionWorks

TM

Connection Data

See the System Status Display table.

Hardware Status
(momentary stop, RUN/
STOP, testing mode,
etc.)

See the System Status Display table.