Zero-point Setting (ZSET)

MotionSuite™ MP940 Machine Controller Reference Manual

11-90

2. Select the position control mode (PCON) (Bit 2 of OWC000).

Note:

Set bit 7 “Motion Command Use Selection” of
fixed motion parameter 14 “Additional Func-
tion Selections” to “Use” (= 1). Alternately, set
bit 8 “Motion Command Code Selection” of
fixed motion parameter 14 “Additional Func-
tion Selections” to “Enabled” (= 1).

3. Set zero-point setting (ZRET = 9) in the motion commands (OWC020).

Note:

The RUN command (bit 1 of OWC001) can be
either ON or OFF. It is possible to execute zero-
point setting (ZSET) during axis motion if
fixed motion parameter 3 “Encoder Selection”
is set to “absolute encoder (= 1)”, and bit 5
“Axis Selection” of fixed motion parameter 17
“Motion Controller Function Selection Flag” is
set to “Infinite Length Axis (= 1)”.

4. Upon feed completion, zero-point setting completion (bit 3 of

IWC015) and zero-point return completion state (bit 6 of IWC015) are
both ON.

ZSET

Start Condition Check

Motion Command Code

= NOP?

return(OK)

YES

YES

NO

NO

YES

NO

Motion Command Response

= NOP?

return(NG)

Motion Command Status

BUSY=OFF?