2 automatic motor data identification, Automatic motor data identification, Automatic motor parameter identification – Lenze 8400 StateLine User Manual

Page 111: Automatic motor, Data identification, 5motor control (mctrl)

Advertising
background image

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

111

5

Motor control (MCTRL)

5.1

Motor selection/Motor data

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.1.2

Automatic motor data identification

The motor parameter identification serves to automatically identify the inverter characteristic, the

influences of the motor cable and various motor parameters.

Automatically identified motor parameters

Automatic calculation of the current controller and field controller parameters

From version 12.00.00 onwards:

Following successful motor parameter identification, the current

controller and field controller parameters listed in the below table are calculated as well.

• If these parameters are not to be calculated, bit 4 of

C02865/1

must be set to "1".

Note!

We strongly recommend motor parameter identification before the initial

commissioning of the sensorless vector control (SLVC) and the sensorless control for

synchronous motors (SLPSM).

Parameter

Info

ASM

PSM

C00015

V/f base frequency

C00016

V

min

boost

C00021

Slip compensation

C00082

Motor rotor resistance

C00083

Motor rotor time constant

C00084

Motor stator resistance

C00085

Motor stator leakage inductance

C00092

Motor magnetising inductance

C00095

Motor magnetising current

Parameter

Info

ASM

PSM

C00073/1

VFC: Vp Imax controller

C00075

Vp current controller

C00076

Ti current controller