20 l_gainoffset_3, L_gainoffset_3, 17 function library – Lenze 8400 StateLine User Manual

Page 938

Advertising
background image

17

Function library

17.1

Function blocks

938

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

17.1.20

L_GainOffset_3

This FB can amplify an analog input signal and then add an offset to it. Preferably to be

interconnected directly after the analog input terminals.

• The internal calculations (addition and subtraction) are carried out with 32 bits without

overflow/underflow. Division is not remainder considered.

• Gain and offset are selected via FB inputs.
• The value provided at the nOut_a output is internally limited to ±199.99 %.

Inputs

Outputs

Function

Identifier

Data type

Information/possible settings

nIn_a

INT

Input signal

• Scaling: 16384 ≡ 100 %

nGain_a

INT

Gain factor

• Scaling: 16384 ≡ 100 %

• 199.99 % ≈2

nOffset_a

INT

Offset

• Scaling: 16384 ≡ 100 %

Identifier

Data type

Value/meaning

nOut_a

INT

Output signal

• Internal limitation to ±199.99 %

/B*DLQ2IIVHWB

Q,QBD

Q2XWBD

Q2IIVHWBD

Q*DLQBD

“

“



nOut_a

nIn_a Gain factor

(

) Offset

+

=