Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

973

17

Function library

17.1

Function blocks

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

nSet_a

INT

Sensor and process setpoint for operating modes 2, 4 and 5

• Scaling: 16384 ≡ 100 %

• Internal limitation to ± 199.99 %

• Display parameter:

C00830/63

nAct_a

INT

Speed or actual sensor value (actual process value)

• Scaling: 16384 ≡ 100 %

• Internal limitation to ± 199.99 %

• Display parameter:

C00830/61

bInAct

BOOL

Deactivate process controller temporarily (stop)

• Changes can be done online.

• Display parameter:

C00833/76

Note: This input is not interconnected in the LA_NCtrl application block.

TRUE

• The current output value is frozen.

• The internal control algorithm is stopped.

• However, a setpoint selected via input nNSet_a is still provided in

operating modes 0/1/4/5.

bIOff

BOOL

Switch off the I-component of the process controller

• Changes can be done online.

• Display parameter:

C00833/77

TRUE The I component of the process controller is set to zero.

nInfluence_a

INT

Limitation of the influencing factor in percent

nInfluence_a serves to limit the influencing factor of the PID controller contained

in the FB to a required value (- 199.99 % ... + 199.99 %).

• Scaling: 16384 ≡ 100 %

• Internal limitation to ± 199.99 %

• Display parameter:

C00830/64

bEnableInfluenceRamp

BOOL

Activate ramp for influencing factor

• Display parameter:

C00833/106

TRUE Influencing factor of the PID controller is ramped up to the

nInfluence_a value.

FALSE Influencing factor of the PID controller is ramped down to "0".

bISet

BOOL

Accept I component nISet_a in PID controller

TRUE The value at the input nISet_a is accepted in the PID controller.

nISet_a

INT

Selection of I component of PID controller

• With a TRUE signal at bISet, the assigned value is accepted in the PID controller.

• Scaling: 16384 ≡ 100 %

• Internal limitation to ± 199.99 %

bPIDOff

BOOL

(from version 06.00.00)

Reset the entire PID controller

TRUE

• The I component of the controller is set to zero.

• The controller output is set to zero.

• The internal control algorithm is stopped.

Identifier

Data type

Information/possible settings