C00006 | motor control, T in, C00006 – Lenze 8400 StateLine User Manual

Page 601: Set in, 15 parameter reference

Advertising
background image

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

601

15

Parameter reference

15.2

Parameter list | C00006

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00006

Parameter | Name:

C00006 | Motor control

Data type: UNSIGNED_8

Index: 24569

d

= 5FF9

h

Selection of the motor control mode

Motor control (MCTRL)

:

Select control mode

Selection list

(Lenze setting printed in bold)

Info

3 SLPSM: Sensorless PSM

From version 10.00.00

This control type is used for the sensorless control of a

synchronous motor.

Sensorless control for synchronous motors

4 SLVC: Vector control

This control type is used for sensorless vector control of

an asynchronous motor.

• The control type requires motor parameters to be set

as exactly as possible!

Sensorless vector control

6 VFCplus: V/f linear

This control type is used for the speed control of an

asynchronous motor via a linear V/f characteristic and is

the simplest control type.

• For setting the V/f characteristic, only the rated

frequency (

C00089

) and the rated voltage (

C00090

) of

the motor have to be entered.

V/f characteristic control

7 VFCplus: V/f linear + encoder

This control type is used for speed control of an

asynchronous motor via a linear V/f characteristic.

• The control type requires a speed feedback via an

encoder mounted to the motor!

• For setting the V/f characteristic, only the rated

frequency (

C00089

) and the rated voltage (

C00090

) of

the motor have to be entered.

V/f control

8 VFCplus: V/f quadr

This control type is used for speed control of an

asynchronous motor via a square-law V/f characteristic.

• For setting the V/f characteristic, only the rated

frequency (

C00089

) and the rated voltage (

C00090

) of

the motor have to be entered.

V/f characteristic control

9 VFCplus: V/f quadr + encoder

This control type is used for speed control of an

asynchronous motor via a square-law V/f characteristic.

• The control type requires a speed feedback via an

encoder mounted to the motor!

• For setting the V/f characteristic, only the rated

frequency (

C00089

) and the rated voltage (

C00090

) of

the motor have to be entered.

V/f control

10 VFCplus: V/f definable

From version 04.00.00

This type of control is used for the speed control of an

asynchronous motor via a user-definable characteristic

with several interpolation points.

• For setting the V/f characteristic, only the rated

frequency (

C00089

) and the rated voltage (

C00090

) of

the motor have to be entered.

V/f characteristic control

Advertising