3commissioning – Lenze 8400 StateLine User Manual

Page 68

Advertising
background image

3

Commissioning

3.9

PC manual control

68

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

How to activate the PC manual control:

1. If an online connection to the controller has not been established yet:

Go online.

2. Select the Application parameters tab from the Workspace.
3. Go to the Overview dialog level and click the PC manual control button.

• First, the following safety note is displayed:

• Click the Cancel button to abort the action and close the dialog box.
• The Timeout monitoring input field serves to adapt the timeout for monitoring the

connection between the PC and the controller.

4. To acknowledge the note and activate PC manual control:

Click the Connect PC manual control button.

• The controller is inhibited via device command (

C00002/16

).

• The PC manual control operator dialog is displayed.

Note!

With active PC manual control:
The online connection between PC and controller is monitored by the controller.

• If the online connection is interrupted longer than the timeout time set (Lenze

setting: 2 s):

• The error response "Fault" takes place, i.e. the motor becomes torqueless and

coasts, if it has not yet been in standstill.

• The "

Ck16: Time overflow manual control

" error message is entered into the

logbook.

PC manual control provides the Motion Control Kernel and the motor interface with all

required control signals and setpoint signals.

• The available application (function block interconnection) is now decoupled from

these interfaces, but is continued to be processed and remains unchanged.

• It does not matter what type of motor control is set in

C00006

.