Current limitation in motor and generator mode
In the various motor control modes, the controller is provided with functions which determine the

dynamic behaviour under load and counteract exceedance of the maximum current in motor or

generator mode.

The current limits must be selected depending on

• the permissible maximum current of the motor  recommendation: I(Mot)

N

< 1.5 ... 2.0

• the permissible maximum current of the inverter
• the torque in motor/generator mode required for the application

Parameter

Info

Lenze setting

Value Unit

C00022

Imax in motor mode

47.00 A

C00023

Imax in generator mode

• 100 % ≡ Imax in motor mode (

C00022

)

100 %

Note!

Highly dynamic applications

(that have e.g. too short acceleration/deceleration times or excessively changing loads)
The overcurrent disconnection may respond (fault message oC1 or oC11) if the setting of

the maximum current in motor mode in

C00022

approximately corresponds to the

maximum permissible value of the respective inverter.
Remedies:

• Increase of the acceleration and deceleration ramp times
• Reduction of the maximum current in motor mode

(C00022

)

• Reduction of the maximum current in generator mode (

C00023

)

• Adaptation of the indirect peak current limitation (procedure depends on the selected

motor control mode, see below)

• Reduction of the reset time of the current limiting controller (

C00074/1

)

Influencing the torque in motor/generator mode
The torque in motor and generator mode can be limited via the nTorqueMotLim and

nTorqueGenLim process signal inputs.

• If V/f characteristic control (VFCplus) is selected, limitation is indirectly performed via

a so-called I

max

controller.

• If sensorless vector control (SLVC) and sensorless control for synchronous motors

(SLPSM) is selected, limitation has a direct effect on the torque-producing current

component.

If keypad control is selected, the nTorqueMotLim and nTorqueGenLim process signals can

be parameterised via

C00728/1...2

.