Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

oC11: Clamp operation active [xx.0123.00071]

Id5: Pole position identification error [xx.0123.00074]

oC13: Maximum current for Fch exceeded [xx.0123.00090]

ot2: Speed controller output limited [xx.0123.00093]

FC01: Switching frequency reduction [xx.0123.00094]

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device indicates that the "CLAMP" overcurrent

limitation has been activated.

• A permanent clamp operation causes an overload

disconnection.

Reduce setpoint generation dynamics or motor load.

Response (Lenze setting printed in bold)

Setting:

C00643/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Pole position identification has not been completed

successfully.

Check parameter setting of the pole position

identification.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has detected a motor current which exceeds

the maximum current limit at permanent switching

frequency of the inverter.

• If a permanent switching frequency inverter is set, a

certain limit arises for the maximum current,

depending on the setting. If this current limit is

exceeded due to a load impulse or overload, an error

message is displayed.

• Observe the maximum current setting depending on

the set switching frequency of the inverter.

• Reduce the required load or setting of the dynamic

switching frequency if necessary.

Response (Lenze setting printed in bold)

Setting:

C00567

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The output of the speed controller has reached the

internal limit value. In this status, the speed controller is

not able anymore to correct the system deviation.

• Only during "Closed loop" operation or with vector

control (SLVC).

• Observe load requirements.

• Correct dimensioning or reduce setpoint generation

dynamics if necessary.

Motor control

Response (Lenze setting printed in bold)

Setting:

C00590

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Load-dependent switching frequency reduction

• Observe load requirements.

• Correct dimensioning or reduce setpoint generation

dynamics if necessary.

Motor control