Device control (DCTRL)

4.2

Device state machine and device states

86

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.2.2

Init

The controller is in this status immediately after switching on its 24 V supply voltage.
In the "Init" status, the operating system is initialised and all device components (communication

module, memory module, power section, etc.) are identified. When identifying the power section, it

is checked first if it is switched on or if the required voltage lies within the tolerance zone,

respectively.

• The inverter is inhibited, i.e. the motor terminals (U, V, W) of the inverter are deenergised.
• The digital and analog inputs are not yet evaluated at this time.
• The bus systems (CAN, PROFIBUS etc.) do not work yet, i.e. communication is not possible.
• The application is not yet processed.
• The monitoring functions are not active yet.
• The controller cannot be parameterised yet and no device commands can be carried out yet.

"DRV-RDY" LED

"DRV-ERR" LED

Display in

C00137

Display in status word 1 (

C00150

)

Bit 11

Bit 10

Bit 9

Bit 8

OFF

OFF

Init

0

0

0

1

Note!

If the 24V voltage supply is in the valid range (>19V) and the initialisation is finished, the

device changes automatically to the "

ReadyToSwitchOn

" status.

If only the 24V voltage supply is available during the mains connection, the error

message "

LU: Undervoltage in the DC bus

" is also entered into the logbook of the drive

controller.