7technology applications – Lenze 8400 StateLine User Manual

Page 334

Advertising
background image

7

Technology applications

7.3

TA "actuating drive speed (AC Drive Profile)"

334

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Motor potentiometer

Alternatively to the input signal nMainSetValue_a (or nAuxSetValue_a in case of local setpoint selection), the speed

setpoint can also be generated via a motor potentiometer function.

• In the Lenze setting, the motor potentiometer function is deactivated.

• Activation is possible via

C00806

or via the bMPotEnable input.

• The behaviour of the motor potentiometer during switch-on of the drive system can be selected in

C00805

.

• For a detailed functional description see the

L_MPot

FB.

bMPotEnable

BOOL

Activating the motor potentiometer function

• This input and

C00806

are OR'd.

TRUE The motor potentiometer function is active; the speed setpoint can

be changed via the bMPotUp and bMPotDown control inputs.

bMPotUp

BOOL

Increasing the speed setpoint

TRUE Approach the upper speed limit value set in

C00800

with the

acceleration time set in

C00802

.

bMPotInAct

BOOL

Activating the inactive function

TRUE The speed setpoint behaves according to the inactive function set in

C00804

.

• In the Lenze setting, the speed setpoint is maintained.

bMPotDown

BOOL

Decreasing the speed setpoint

TRUE Approach the lower speed limit value set In

C00801

with the

deceleration time set in

C00803

.

Process controller

• In the Lenze setting, the process controller is deactivated.

• The activation is executed by selecting the operating mode in

C00242

.

• For a detailed functional description see FB

L_PCTRL

.

bPIDEnableInfluenceRamp

BOOL

Activate ramp for influencing factor

FALSE Influencing factor of the PID controller is ramped down to "0".

TRUE Influencing factor of the PID controller is ramped up to the value

nPIDInfluence_a.

bPIDIOff

BOOL

Switch off the I-component of the process controller

• In conjunction with the operating mode set in

C00242

(Lenze setting: "Off").

TRUE I-component of the process controller is switched off.

nPIDVpAdapt_a

INT

Adaptation of gain Vp set in

C00222

in percent

• Scaling: 16384 ≡ 100 %

• Internal limitation to ± 199.99 %

• Changes can be done online.

nPIDSetValue_a

INT

Sensor and process setpoint for operating modes 2, 4 and 5

• Scaling: 16384 ≡ 100 %

• Internal limitation to ± 199.99 %

nPIDActValue_a

INT

Speed or actual sensor value (actual process value)

• Offset and gain for this input signal can be set in

C00698

and

C00672

.

• Scaling: 16384 ≡ 100 %

• Internal limitation to ± 199.99 %

nPIDInfluence_a

INT

Limitation of the influencing factor in percent

• The influence factor of the PID controller can be limited to a certain value (-

199.99% ... + 199.99%) via nPIDInfluence_a.

• Scaling: 16384 ≡ 100 %

• Internal limitation to ± 199.99 %

Identifier

Data type

Information/possible settings

Advertising