3.2

Notes on motor control

In the Lenze setting, the V/f characteristic control (VFCplus) as motor control is set in

C00006

with

a linear characteristic.

• V/f characteristic control (VFCplus) is a motor control mode for classic frequency inverter

applications on the basis of a simple and robust control procedure for the operation of machines

with a linear or quadratic load torque characteristic (e.g. fans).

• The presettings of the parameters ensure that the controller is immediately ready for operation

and the motor works adequately without further parameterisation if a controller and a 50 Hz

asynchronous machine with matching performances are assigned to each other.

Recommendations for the following application cases:

• If the controller and motor differ greatly in terms of performance:

Set the Imax limit (in motor mode) in

C00022

to 2x rated motor current.

• If a high starting torque is required:

When the motor is idling, set a value for Vmin boost in

C00016

which ensures that the rated

motor current flows at a field frequency of f = 3 Hz (display in

C00058

).

• For noise optimisation:

In

C00018

, set a switching frequency of "16 kHz var./drive-opt.".

• If a high torque must be provided at small speeds without feedback:

Select "Sensorless vector control (SLVC) as motor control mode in

C00006

.

Related topics:

Motor control (MCTRL)

( 104)

Note!

Check the nameplate data against the motor data set in the controller. Further

information is provided in the chapter "

Motor selection/Motor data

".

( 105)