5

Motor control (MCTRL)

5.6

V/f control (VFCplus + encoder)

154

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.6

V/f control (VFCplus + encoder)

The V/f characteristic control (VFCplus) described above can be operated with a speed feedback.

This has the following advantages:

• Steady-state accuracy of the speed
• Less parameterisation effort compared to the sensorless vector control (SLVC)
• Improved dynamics compared to V/f characteristic control without feedback or to sensorless

vector control (SLVC).

• Suitability for group drives

Stop!

The V/f control requires a speed feedback!

• The speed sensor used has to be set in

C00495

. This setting is not made automatically

with the selection of the motor from the »Engineer« motor catalogue!

• If no speed sensor is set in

C00495

and the controller is enabled, an impermissibly

high motor current occurs which may destroy the motor thermally!

From version 14.00.00

, the error response set in

C00571/2

(Lenze setting: "Fault")

takes place if in case of controller enable it is detected that a motor control type with

feedback is set in

C00006

but no speed encoder is set in

C00495

.

Stop!

V/f emergency operation

From version 15.00.00

, it is internally switched to the encoderless V/f characteristic

control in case of an encoder open circuit in order to avoid impermissible motor

movements.

• In order that this "V/f emergency operation" works properly, the parameters relevant

for the V/f characteristic control (base frequency, Vmin boost, slip compensation, etc.)

have to be set correctly. As an alternative, a motor parameter identification can be

executed as well.

• The change-over to "V/f emergency operation" is reported via bit 4 in

C01000

and via

the bWirebreakUfLinearActive status signal at the SB

LS_DeviceMonitor

.

• The change-over to "V/f emergency operation" can be suppressed by setting bit 8 to

"1" in

C02864/1

.

Note!

• Make sure that, when the motor control with speed feedback is in use, the maximum

input frequency of 10 kHz is not exceeded.

Using DI1 and DI2 as frequency inputs

( 266)

• As the slip is calculated in the feedback V/f operation and injected through the slip

regulator, the slip compensation (

C00021

) is deactivated with V/f control.