Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

655

15

Parameter reference

15.2

Parameter list | C00271

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00271

C00272

C00273

C00274

C00275

Parameter | Name:

C00271 | SC: Width of current setpoint filter

Data type: UNSIGNED_16

Index: 24304

d

= 5EF0

h

Frequency width of the current setpoint filter with sensorless control for synchronous motors (

SLPSM

)

• Width around the frequency to be inhibited (

C00270

).

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

Hz

500.0 0.0 Hz

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00272 | SC: Depth of current setpoint filter

Data type: UNSIGNED_16

Index: 24303

d

= 5EEF

h

Damping of the current setpoint filter with sensorless control for synchronous motors (

SLPSM

)

Setting range

(min. value | unit | max. value)

Lenze setting

0

dB

100 0 db

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00273 | Moment of inertia motor

Data type: UNSIGNED_32

Index: 24302

d

= 5EEE

h

From version 03.00.00

Moment of inertia for setpoint feedforward control with sensorless vector control (

SLVC

)

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

kg cm^2

6000000.00 0.00 kg cm^2

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00274 | SC: Max. change in acceleration

Data type: UNSIGNED_16

Index: 24301

d

= 5EED

h

Limitation of the acceleration change with sensorless control for synchronous motors (

SLPSM

)

• Setting in % of M_Nenn per ms.

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

%/ms

400.0 400.0 %/ms

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00275 | Filter setpoint feedforward control

Data type: UNSIGNED_16

Index: 24300

d

= 5EEC

h

From version 03.00.00

Filter time of the setpoint feedforward control with sensorless vector control (

SLVC

)

• The setpoint feedforward control requires the entry of the moment of inertia in

C00273

.

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

ms

1000.0 1.0 ms

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10