725

15

Parameter reference

15.2

Parameter list | C00640

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00640

C00643

C00653

Parameter | Name:

C00640 | L_NSet_1: nNOut_a

Data type: INTEGER_16

Index: 23935

d

= 5D7F

h

The

L_NSet_1

FB: Display of the generated main speed setpoint at the output nNOut_a

Display range

(min. value | unit | max. value)

-199.99

%

199.99

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00643 | Resp. to PLI monitoring

Data type: UNSIGNED_8

Index: 23932

d

= 5D7C

h

From version 11.00.00

Pole position identification without motion

Selection list

0 No Reaction
1 Fault
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information

Subcodes

Lenze setting

Info

C00643/1

1: Fault

Response to PLI monitoring

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00653 | Sensibility - Setpoint feedforward control

Data type: UNSIGNED_8

Index: 23922

d

= 5D72

h

From version 12.00.00

Selection of the sensitivity of the differential setpoint feedforward control

• Depending on the selection, the number of indicated higher-order bits is evaluated.

Note:

The most significant bit determines the sign of the value, the remaining bits determine the numerical value.
Selection list

Info

0 Inactive
1 15 bits

Bit 0 ... bit 14 are evaluated

2 14 bits

Bit 0 ... bit 13 are evaluated

3 13 bits

Bit 0 ... bit 12 are evaluated

4 12 bits

Bit 0 ... bit 11 are evaluated

5 11 Bit

Bit 0 ... bit 10 are evaluated

6 10 Bit

Bit 0 ... bit 9 are evaluated

7 9 Bit

Bit 0 ... bit 8 are evaluated

Subcodes

Lenze setting

Info

C00653/1

0: Inactive

Sensibility - Setpoint feedforward control

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1