7

Technology applications

7.4

TA "Switch-off positioning"

368

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

7.4.2.1

Truth table for activating the pre-switch off

[7-1]

Truth table for activating the pre-switch off

Input

Function

Response in the setpoint generator

(FB L_NSet)

bJogCtrl

InputSel1

bJogCtrl

InputSel2

FALSE

FALSE

Pre-switch off inactive

No response

• The input signal bJogCtrlRfgIn is output

directly at output bRfgOut.

• The input signals bJogCtrlJog1 and

bJogCtrlJog2 are passed through 1:1 to

the downstream FB

L_NSet

for the

selection of fixed setpoints.

TRUE

FALSE

The bJogCtrlSlowDown1 and

bJogCtrlStop1 inputs are evaluated.

Pre-switch off can be activated

• If the slowdown function is activated via

the selected bJogCtrlSlowDown input,

fixed setpoint 2 is activated in the

setpoint generator.

• If the stop function is activated via the

selected bJogCtrlStop input, the setpoint

generator is deactivated.

FALSE

TRUE

The bJogCtrlSlowDown2 and

bJogCtrlStop2 inputs are evaluated.

TRUE

TRUE

The inputs bSJogCtrllowDown3 and

bJogCtrlStop3 are evaluated.