9

Diagnostics & error management

9.7

Maloperation of the drive

442

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

An asynchronous

motor with feedback

rotates without

control and with too

low speed

Motor phases have been interchanged

• Thus the rotating field of the motor is not

identical anymore with the rotating field

of the feedback system.

• Therefore, the drive shows the following

behaviour if V/f characteristic control

(

C00006

= 7) is performed:

• The motor rotates faster than the speed

setpoint by the value set in

C00074

.

• After the controller has been enabled,

the controller will not stop if the speed

setpoint = 0 or a quick stop (QSP)

occurs.

• Among other things, the final motor

current depends on the value set for the

V

min

boost and may rise up to I

max

which can trigger the "oC5: Ixt

overload" fault message.

Check the phase position of the motor cable

If possible: Actuate the motor with

deactivated feedback (

C00006

= 6) and check

direction of rotation of the motor

Motor phase (LP1)

monitoring does not

respond if the motor

phases are

interrupted

Monitoring is not active (

C00597

= 0)

Activate monitoring (

C00597

= 1)

Maloperation

Cause

Remedy