3 automatic restart after mains connection/fault, 1 "inhibit at power-on" auto-start option, Automatic restart after mains connection/fault – Lenze 8400 StateLine User Manual

Page 95: Inhibit at power-on" auto-start option, 4device control (dctrl), Danger

Advertising
background image

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

95

4

Device control (DCTRL)

4.3

Automatic restart after mains connection/fault...

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.3

Automatic restart after mains connection/fault...

.../Error/undervoltage/loading of the Lenze setting
In

C00142

, the starting performance of the controller after mains connection, undervoltage, loading

of the Lenze setting as well as a "

Trouble

" or a "

Fault

" reset can be parameterised individually:

4.3.1

"Inhibit at power-on" auto-start option

The auto-start option "Inhibit at power-on" prevents the change to the "

SwitchedOn

" status after

mains connection if the controller is already enabled at mains connection.

The following three cases describe the behaviour of the controller after mains connection

depending on whether the controller is enabled and the set auto-start option. Here, it is assumed

that after mains connection, no errors and trouble occur in the controller and the "EnableOperation"

control bit in the wDriveControl is set to "1".

Auto-start option (

C00142

)

Lenze setting

Bit 0

"Inhibit at power-on" auto-start option

1 ≡ Inhibit is active

Bit 1 Inhibit at trouble

0 ≡ Inhibit is not active

Bit 2 Inhibit at fault

0 ≡ Inhibit is not active

Bit 3 Inhibit at undervoltage

1 ≡ Inhibit is active

Bit 4

Auto-start option "Inhibit at Lenze setting"

(from version 06.00.00)

1 ≡ Inhibit is active

Bit 5 Reserved

0

Bit 6
Bit 7

Note!

In the Lenze setting

, automatic restart after mains connection, undervoltage, and

loading of the Lenze setting is inhibited.

Danger!

If the "Inhibit at power-on" auto-start option has been deactivated in

C00142

, (bit 0 = 0),

the motor can directly start to run if the controller is enabled after mains connection!