C00980 | output power, C00981 | energy display, C00982 | vfc-eco: voltage reduction ramp – Lenze 8400 StateLine User Manual

Page 770: C00983 | delay, C00982, C00980/1, C00980/2, C00981/1, C00981/2, Setting in

Advertising
background image

15

Parameter reference

15.2

Parameter list | C00980

770

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00980

C00981

C00982

C00983

Parameter | Name:

C00980 | Output power

Data type: INTEGER_32

Index: 23595

d

= 5C2B

h

From version 10.00.00

Display parameter for an energy analysis in the prevailing application. From this, decisions can be deduced whether

a measure for energy optimisation is economic.
Display range

(min. value | unit | max. value)

-32.000

kW

32.000

Subcodes

Info

C00980/1

Active output power

C00980/2

Apparent output power

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00981 | Energy display

Data type: INTEGER_32

Index: 23594

d

= 5C2A

h

From version 10.00.00

Display parameter for an energy analysis in the prevailing application. From this, decisions can be deduced whether

a measure for energy optimisation is economic.

• The values are saved to the device by switching off the mains and cannot be reset.

Display range

(min. value | unit | max. value)

0.00

kWh

21474836.47

Subcodes

Info

C00981/1

Output energy in motor mode

C00981/2

Output energy in generator mode

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00982 | VFC-ECO: Voltage reduction ramp

Data type: UNSIGNED_8

Index: 23593

d

= 5C29

h

From version 10.00.00

Voltage ramp for cancelling V-Sub with energy-saving V/f characteristic control (

VFCplusEco

)

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

s

5.0 0.8 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00983 | Delay

Data type: UNSIGNED_16

Index: 23592

d

= 5C28

h

Setting range

(min. value | unit | max. value)

0

ms

4000

Subcodes

Lenze setting

Info

C00983/1

50 ms

Delay Imax

C00983/2

1000 ms

VFC

: Voltage ramp after overvoltage oU

From version 15.00.00

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1