_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

oC10: Maximum current reached [xx.0123.00030]

oC17: Clamp sets pulse inhibit [xx.0123.00031]

oS1: Maximum speed limit reached [xx.0123.00032]

oS2: Max. motor speed [xx.0123.00033]

Id1: Motor data identification error [xx.0123.00057]

Response (Lenze setting printed in bold)

Setting:

C00609

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device displays that the maximum current has been

reached.

• Check and, if required, correct dimensioning of the

load with regard to the installed device power.

• Check the maximum current settings in

C00022

(Imax in motor mode) and

C00023

(Imax in generator

mode).

Response (Lenze setting printed in bold)

Setting:

C00569/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Due to a short overcurrent, the inverter was switched off

for a short time (clamp disconnection).

• Check and, if required, correct dimensioning of the

load with regard to the installed device power.

• Reduce the dynamics of the setpoint change or speed

control.

Response (Lenze setting printed in bold)

Setting:

C00579

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has recognised that the maximum speed has

been reached.

• Limit setpoint selection to maximum values.

• Adjust set speed limitation (

C00909

) and frequency

limitation (

C00910

).

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has recognised that the maximally

permissible motor speed has been reached.

• Limit setpoint selection to the maximally permissible

motor speed.

• If required, adapt set maximum motor speed

(

C00965

).

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

During the identification of motor parameters, an error

has occurred.

Possible causes:

• Interrupted motor cable.

• Switched-off power section during the identification.

• Implausible start parameter settings.

• Check the motor connections and the corresponding

plug connector on the device and, if necessary, the

motor terminal box.

• Correct start parameters for the motor parameter

identification (motor nameplate data).

• Stable power supply of the device.