333

7

Technology applications

7.3

TA "actuating drive speed (AC Drive Profile)"

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

bRLQCcw

BOOL

Activate counter-clockwise rotation (fail-safe)

Input only effective in case of local control (NetCtrl=0)

• For a detailed functional description see the

L_RLQ

FB.

FALSE Quick stop

TRUE Counter-clockwise rotation

nMainSetValue_a

INT

Speed setpoint via fieldbus in [rpm]

Input only effective in case of setpoint selection via fieldbus (NetRef=1)

• This input is evaluated with the speed scaling set in

C01353/1

(AC Drive Attribute

22).

Scaling of speed and torque values

• An absolute value is created internally (the sign has no meaning).

• Offset and gain of this input signal can be set in

C00696

and

C00670

for a simple

signal adjustment of a setpoint encoder.

• The setpoint is transformed to a speed setpoint in the setpoint encoder via a

ramp function generator with linear or S-shaped ramps.

• Upstream to the ramp function generator, a blocking speed masking function

and a setpoint MinMax limitation are effective.

• For a detailed functional description see the

L_NSet

FB.

nAuxSetValue_a

INT

Local speed setpoint (speed mode) or torque setpoint (torque mode)

• Input only effective in case of local setpoint selection (NetRef=0)

When "speed mode" is set, the following applies:

• The input value is interpreted as speed setpoint.

• Scaling: 16384 ≡ 100 % reference speed (

C00011

)

• Offset and gain of this input signal can be set in

C00696

and

C00670

for a simple

signal adjustment of a setpoint encoder.

• The setpoint is transformed to a speed setpoint in the setpoint encoder via a

ramp function generator with linear or S-shaped ramps.

• Upstream to the ramp function generator, a blocking speed masking function

and a setpoint MinMax limitation are effective.

• For a detailed functional description see the

L_NSet

FB.

When "torque mode" is set, the following applies:

• The input value is interpreted as torque setpoint.

(Input nAuxSetValue_a is internally connected to input nTorqueGenLim_a).

• Scaling: 16384 ≡ 100 % M

max

(

C00057

)

• The speed setpoint is internally permanently set to "100 %".

bJogSpeed1

bJogSpeed2

BOOL

Selection inputs for override fixed setpoints (JOG setpoints)

Inputs only effective in case of local setpoint selection (NetRef=0)

• These selection inputs can be used to activate a fixed setpoint for the setpoint

generator instead of the setpoint applied to the nAuxSetValue_a input.

• The four selection inputs are binary coded, therefore 15 fixed setpoints can be

selected.

• In case of binary coded selection "0" (all inputs = FALSE or not assigned), the main

setpoint applied to the nAuxSetValue_a input is active.

• The selection of the fixed setpoints is carried out in

C00039/1...15

in [%] based

on the reference speed (

C00011

).

• For a detailed functional description see the

L_NSet

FB.

bJogSpeed4

bJogSpeed8

BOOL

bJogRamp1

bJogRamp2

BOOL

Selection inputs for alternative acceleration/deceleration times

• The four selection inputs are binary coded, therefore 15 alternative

acceleration/deceleration times can be selected.

• In case of binary selection "0" (all inputs = FALSE or not assigned), the acceleration

time (

C00012

) and deceleration time (

C00013

) set for the main setpoint are

active.

• Alternative acceleration times are selected in

C00101/1...15

.

• The selection of the alternative deceleration times is carried out in

C00103/1...15

.

• For a detailed functional description see the

L_NSet

FB.

bJogRamp4

bJogRamp8

BOOL

Identifier

Data type

Information/possible settings

Advertising