C00801 | l_mpot_1: lower limit, C00802 | l_mpot_1: acceleration time, C00803 | l_mpot_1: deceleration time – Lenze 8400 StateLine User Manual

Page 742: C00804 | l_mpot_1: inactive fct, C00805 | l_mpot_1: init fct, C00805, C00802, C00804, C00801, T in

Advertising
background image

15

Parameter reference

15.2

Parameter list | C00801

742

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00801

C00802

C00803

C00804

C00805

Parameter | Name:

C00801 | L_MPot_1: Lower limit

Data type: INTEGER_16

Index: 23774

d

= 5CDE

h

The

L_MPot_1

FB: Lower limit of the motor potentiometer function

Setting range

(min. value | unit | max. value)

Lenze setting

-199.99

%

199.99 -100.00 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00802 | L_MPot_1: Acceleration time

Data type: UNSIGNED_16

Index: 23773

d

= 5CDD

h

The

L_MPot_1

FB: Acceleration time of the motor potentiometer function

Setting range

(min. value | unit | max. value)

Lenze setting

0.1

s

6000.0 10.0 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00803 | L_MPot_1: Deceleration time

Data type: UNSIGNED_16

Index: 23772

d

= 5CDC

h

The

L_MPot_1

FB: Deceleration time of the motor potentiometer function

Setting range

(min. value | unit | max. value)

Lenze setting

0.1

s

6000.0 10.0 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10

Parameter | Name:

C00804 | L_MPot_1: Inactive fct.

Data type: UNSIGNED_8

Index: 23771

d

= 5CDB

h

The

L_MPot_1

FB: Selection of the response if the motor potentiometer is deactivated via input bInAct

Selection list

(Lenze setting printed in bold)

Info

0 Retain value

Keep output value

1 Deceleration to 0

Deceleration via ramp to 0

2 Deceleration to lower limit

Deceleration via ramp to the lower limit (

C00801

)

3 Without ramp to 0

Step change to 0

4 Without ramp to lower limit

Jump to lower limit (

C00800

)

5 Acceleration to upper limit

Acceleration via ramp to upper limit (

C00800

)

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00805 | L_MPot_1: Init fct.

Data type: UNSIGNED_8

Index: 23770

d

= 5CDA

h

The

L_MPot_1

FB: Selection of the response at device switch-on

Selection list

(Lenze setting printed in bold)

0 Load last value
1 Load lower limit
2 Load 0

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1