Motor control (MCTRL)

5.11

Braking operation/brake energy management

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Using the integrated brake chopper
We recommend to use the brake chopper (brake transistor) which is integrated into the controller

for the braking operation, regardless of the selected motor mode.

• Connect the required brake resistor to the R

B1

and R

B2

terminals of the controller.

• In

C00175

, a ramp function generator stop (FB

L_NSet_1

) can be set for instances when the

brake resistor is controlled. This prevents overvoltage deactivation in the case of short

deceleration times.

Selecting the response to an increase of the DC-bus voltage

( 229)

DC-bus system
For a DC-bus connection with other devices, we recommend to connect the regenerative power

supply module to terminals +UG and –UG.

Note!

The brake transistor will be switched off if it remains switched on for a period of 4

seconds.

• If the DC-bus voltage falls under the brake chopper threshold for a short time again,

the brake transistor can switch on again for a maximum of 4 seconds, without

interruption.

• This protective function is used to prevent the brake chopper from being switched on

permanently due to e.g. too high voltages at all times or incorrect interconnection of

the bBrakeChopperOn signal

(from version V12.00.00)

.

From version 14.00.00

, the limitation of the operating time can be deactivated to

max. 4 seconds. For this purpose, set bit 1 to "1" in

C02864/1

.

The integrated brake chopper is always triggered via the DC-bus voltage with

exceedance of the "voltage threshold for braking operation" independent of the device

status.

From version 14.00.00

, the brake chopper can also be switched off at pulse inhibit or

when the "Fault" device status is activated.

• For a switch-off at pulse inhibit, set bit 7 to "1" in

C02865/1

.

• For a switch-off in the "Fault" device status, set bit 2 to "1" in

C02864/1

.

Note!

DC-bus system without the use of a regenerative module:

Up to and including version V11.xx.xx

, only one internal brake chopper can be used in

the DC-bus system to dissipate regenerative energy.

From version V12.00.00

, all internal brake choppers can be used in the DC-bus system

to dissipate regenerative energy ("Master-slave operation").

Control of multiple

internal brake choppers in the DC-bus system

( 234)

In order to install the regenerative module, follow the notes in the 8400 hardware

manual. The hardware manual has been stored in electronic form on the data carrier

supplied with the 8400 controller.