Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

229

5

Motor control (MCTRL)

5.11

Braking operation/brake energy management

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.11.1

Setting the voltage source for braking operation

The voltage threshold for braking operation is set via the mains voltage (

C00173

) and the reduced

brake chopper threshold (

C00174

). When this "brake chopper threshold" is exceeded, the response

selected in

C00175

takes place in the DC bus. The selected function (e.g. use of a brake resistor)

serves to dissipate energy in the DC bus and reduce the DC-bus voltage.

• The "brake chopper threshold" is preset as follows so that it is higher than the specified mains

voltage (

C00173

):

• This brake chopper threshold can be reduced by 0 ... 150 V by means of

C00174

.

Example:

• A 400 V device has a maximum mains voltage of 420 V AC.

• Maximum stationary DC-bus voltage: 420 V AC * 1.414 = 594 V DC

C00173

has been set with the selection "0" for 400 V AC mains.

• This means that

C00174

can be set to a maximum of 131 V DC (725 V DC - 594 V DC).

5.11.2

Selecting the response to an increase of the DC-bus voltage

If the brake chopper threshold resulting from

C00173

and

C00174

is exceeded in the DC bus, the

reaction selected in

C00175

takes place (use of the brake resistor and/or stop of the ramp function

generator and/or inverter-motor brake).

• Optimum following of the actual speed value until the speed setpoint is reached (e.g. the motor

is stopped rapidly) is always achieved with the help of a brake resistor.

• Stopping the ramp function generator enables smoother deceleration with lower torque

oscillation..

• The inverter motor brake is available in

C00175

from version 04.00.00 onwards

. This function

enables rapid braking without a brake resistor. Torque oscillations can occur due to the

traversing dynamics.

Inverter motor brake

( 231)

Mains voltage

Brake chopper threshold

C00173

1-phase

3-phase

1-phase

3-phase

0

1ph 230V

3ph 400V

DC380V

DC725V

1

1ph 230V

3ph 440V

DC380V

DC735V

2

1ph 230V

3ph 480V

DC380V

DC775V

3

1ph 230V

3ph 500V

DC380V

DC790V

Stop!

The brake chopper threshold resulting from

C00173

and

C00174

must not exceed the

stabilised DC-bus voltage!