5

Motor control (MCTRL)

5.5

V/f characteristic control - energy-saving (VFCplusEco)

152

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.5.5

Remedies for undesired drive behaviour

Drive behaviour

Remedy

Inadequate smooth running at low speeds, especially in

the case of operation with a long motor cable

Automatic motor data identification ( 111)

Reduce the influence of the Eco function by increasing

the minimum voltage V/f (

C00977

) if necessary.

Problems in case of high starting duty (great mass

inertia)

1.Set motor control VFCplus with linear characteristic

(

C00006

= 6).

2.

Adapting the Vmin boost

.

( 135)

3.Again set motor control VFCplusEco (

C00006

= 11).

Drive does not follow the speed setpoint

The current controller intervenes in the set field

frequency to limit the controller output current to the

maximum current (C0022, C0023). Therefore:

• Prolong acceleration/deceleration times:

C00012:

Accel. time - main setpoint

C00013

: Decel. time - main setpoint

• Consider a sufficient magnetising time of the motor.

Depending on the motor power, the magnetising

time amounts to 0.1 ... 0.2 s.

• Increase the maximally permissible current:

C00022

: Imax in motor mode

C00023

: Imax in generator mode

• Make adaptations for the Eco function:

Improving the behaviour at high dynamic load

changes

.

( 150)

Adapting the slope limitation for lowering the Eco

function

.

( 151)

Optimising the cos/phi controller

.

( 151)

Insufficient speed constancy at high load (setpoint and

motor speed are not proportional anymore)

• Increase slip compensation (

C00021

).

Important: Unstable drive due to overcompensation!

• With cyclic load impulses (e. g. centrifugal pump), a

smooth motor characteristic is achieved by smaller

values in

C00021

(possibly negative values).

Note: The slip compensation is only active for operation

without speed feedback.

"Clamp operation active" error message (oC11):

Controller cannot follow dynamic processes, i.e. too

short acceleration/deceleration times in terms of load

ratios.

• Increase the gain of the I

max

controller (

C00073

)

• Reduce the reset time of the I

max

controller (

C00074

)

• Prolong the acceleration time (

C00012

)

• Prolong the deceleration time (

C00013

)

• Make adaptations for the Eco function:

Improving the behaviour at high dynamic load

changes

.

( 150)

Adapting the slope limitation for lowering the Eco

function

.

( 151)

Motor stalling in the field weakening range

(adaptation especially required for small machines)

• If motor power < inverter power:

Set

C00022

to I

max

= 2 I

rated motor

• Reduce dynamic performance of setpoint generation

• Make adaptations for the Eco function:

Improving the behaviour at high dynamic load

changes

.

( 150)

Adapting the slope limitation for lowering the Eco

function

.

( 151)

Speed variations in no-load operation for speeds > 1/3

rated speed.

Minimise speed oscillations with oscillation damping

(

C00234

).