C01082 | ls_writeparamlist: execute mode, C01083 | ls_writeparamlist: error status, C01084 | ls_writeparamlist: error line – Lenze 8400 StateLine User Manual

Page 776: C01083, Displays an, C01084, C01082, 15 parameter reference

Advertising
background image

15

Parameter reference

15.2

Parameter list | C01082

776

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C01082

C01083

C01084

Parameter | Name:

C01082 | LS_WriteParamList: Execute Mode

Data type: UNSIGNED_8

Index: 23493

d

= 5BC5

h

From version 04.00.00

Parameter change-over

: Selection of the activation method

Selection list

(Lenze setting printed in bold)

Info

0 by Execute

The writing of the parameter list is activated by a

FALSE/TRUE edge at the bExecute input.

1 by Input Select

The writing of the parameter list is carried out if a change

is made at the select inputs and if the controller is

initialised.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01083 | LS_WriteParamList: Error status

Data type: UNSIGNED_16

Index: 23492

d

= 5BC4

h

From version 04.00.00

Parameter change-over

: Error status:

• 0 = no error

• 33803 | 0x840B = invalid data type (e.g. STRING)

• 33804 | 0x840C = limit violation

• 33806 | 0x840E = invalid code

• 33813 | 0x8415 = no element of the selection list

• 33815 | 0x8417 = writing of the parameter not permitted

• 33816 | 0x8418 = writing of the parameter only permitted if controller is inhibited

• 33829 | 0x8425 = invalid subcode

• 33865 | 0x8449 = no parameter with subcodes

Display range

(min. value | unit | max. value)

0

34000

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01084 | LS_WriteParamList: Error line

Data type: UNSIGNED_8

Index: 23491

d

= 5BC3

h

From version 04.00.00

Parameter change-over

: Display of the number of list entry where the error occurred (in connection with the value

set selected via bSelectWriteValue_1 and bSelectWriteValue_2).
Display range

(min. value | unit | max. value)

0

32

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1