System bus "CAN on board"

11.11

Implemented CANopen objects | I-1005

546

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

I-1005

This object can be used to activate the generation of sync telegrams and to write the identifier

value.

• This object relates to codes

C00367

and

C00368

.

Creating sync telegrams
Sync telegrams are created by setting bit 30 (see below) to "1". The time between the sync telegrams

can be set using the object

I-1006

.

Writing identifiers
To receive PDOs, the value 0x80 must be entered in the 11-bit identifier in the Lenze setting (and

according to CANopen specification) . This means that all modules are by default set to the same

sync telegram.

• If sync telegrams are only to be received by certain communication modules, their identifiers

can be entered with values up to and including 0x07FF.

• The identifier can only be changed if the communication module does not send any sync

telegrams (bit 30 = "0").

• How to change the identifier:

• Deactivate identifier (set bit 30 to "0").
• Change identifier.
• Activate identifier (set bit 30 to "1").

[11-2] Data telegram assignment

Index:

I-1005

Name:

COB-ID SYNC message

Subindex

Default setting

Setting range (min. value | unit | max. value)

Access

Data type

0: COB-ID SYNC message

0x0000 0080

or

0x8000 0080

0

4294967295 rw

U32

8th byte

7th byte

6th byte

5th byte

Data 4

Data 3

Data 2

Data 1

Bit 31

Bit 30

Bit 29 ... bit 11

Bit 10 ... bit 0

X

0/1

Extended identifier*

11-bit identifier

* The extended identifier is not supported. Bit 11 ... bit 29 must be set to "0".