2 signal monitoring, Signal monitoring, Signal monitoring ( 941) – Lenze 8400 StateLine User Manual

Page 941: 17 function library

Advertising
background image

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

941

17

Function library

17.1

Function blocks

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

17.1.21.2 Signal monitoring

If signal monitoring is active (

C00950/2

= 1), the signal characteristic of the dnPhIn_p input signal

is continued even if the data telegram is missing (setpoint selection via CAN).
Monitoring is performed on the basis of the dnPhIn_p position setpoint and the bSpeedAct0 status

signal:

• If the dnPhIn_p position setpoint remains the same in the next device cycle, it is either because

the speed is zero or because no data telegram has been received.

• The evaluation of the bSpeedAct0 status signal gives information about which reason applies.

This status signal needs to be transmitted by the setpoint source to ensure trouble-free

operation:

bSpeedAct0 = FALSE means that the speed is not zero, so an error is assumed: The signal

characteristic of the dnPhIn_p input signal is completed (the current slope is retained).

bSpeedAct0 = TRUE means that the speed is zero, so the unchanged position setpoint is not

treated as an error.

• If the number of missing data telegrams exceeds the limit value parameterised in

C00952

, the

bSignalError output is set to TRUE.

• The bSignalError output is automatically reset to FALSE if correct signals are detected at

dnPhIn_p and bSpeedAct0 again.

Note!

Do not change the number of interpolation steps during operation. Otherwise the

interpolation becomes inaccurate.

Note!

The nNIn_a

analog value is not monitored!

Advertising