Function library

17.1

Function blocks

944

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

17.1.23

L_MPot_1

This FB replaces a hardware motor potentiometer and can be used as an alternative setpoint source

which is controlled via two inputs.

• The signal is output via a ramp function generator with linear ramps.
• The acceleration and deceleration times are set via parameters.
• Constant ramping even with speed limit values changed online.
• The motor potentiometer function can be switched on/off online.

Inputs

Identifier

Data type

Information/possible settings

bEnable

BOOL

Switch over motor potentiometer function

bEnable input and

C00806

code are ORed.

TRUE Motor potentiometer function is active, setpoint can be changed via

bUp and bDown.

• With switching to TRUE, the value applied to nIn_a is

automatically transferred to the motor potentiometer.

FALSE The value applied to nIn_a is output at nOut_a.

nln_a

INT

When bEnable = FALSE, the analog nIn_ is input signal switched to the nOut_a

output.

bUp

BOOL

Approaching of the upper speed limit value set in

C00800

.

TRUE The nOut_a output signal runs to its upper limit value (nHighLimit).

• If the bDown input is simultaneously set to TRUE, the nOut_a

output signal is not changed.

bDown

BOOL

Approaching of the lower speed limit value set in

C00801

.

TRUE The nOut_a output signal runs to its lower limit value (nLowLimit).

• If the bUp input is simultaneously set to TRUE, the nOut_a output

signal is not changed.

bInAct

BOOL

Deactivate motor potentiometer function

• This input has the highest priority.

• When the motor potentiometer is deactivated, the nOut_a output signal follows

the function set with code

C00804

.

TRUE Motor potentiometer function is deactivated.