3 reset error message, Reset error message, 9diagnostics & error management – Lenze 8400 StateLine User Manual

Page 448

Advertising
background image

9

Diagnostics & error management

9.9

Error messages of the operating system

448

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Error ID

8-bit value (0 ... 255) for error identification within the error subject area.

Tip!
All possible 16-bit error numbers are listed in the table "

Short overview (A-Z)

" in the second

column.

( 450)

9.9.3

Reset error message

An error message with the response "Fault", "Trouble", "TroubleQSP" or "Warning locked" must be

explicitly reset (acknowledged) after the cause of the error has been eliminated.

To reset (acknowledge) a pending error message, execute device command

C00002/19

= "1".

Tip!
When an online connection to the controller has been established, use the Diagnostics tab

of »Engineer« and click Reset error to reset a pending error message.

35

CAN process data object (PDO)

Errors that are explicitly only related to the CAN-PDO (process data

objects).

Yes

40

Device configuration

Errors that occur due to incompatibilities of the plugged-in individual

components (fieldbus module, safety module, et al.).

Yes if the error relates to a

module plugged-in by the

user.

44

Parameter set

Errors that occur in connection with the parameter set or the

parameter set memory (memory module).

Yes if the error relates to a

missing or incompatible

memory module.

45

Device firmware (internal error)

Internal error of the device firmware.

No

54

Fieldbus

Errors that occur in connection with fieldbus communication.

Yes

84

MotionControlKernel

Errors that occur within the MotionControl basic functions (e.g.

profile generation, brake control, positioning).

Yes

100

...

103

User error 1

...

User error 4

Errors generated by the user (by the application) via the

LS_SetError_1

system block.

Yes

Error subject area

Assigned errors

Remedy possible by

user?

No.

Name

8

14

Bit15

0

7

Advertising