2 deactivate motor potentiometer, Deactivate motor potentiometer, 17 function library – Lenze 8400 StateLine User Manual

Page 947

Advertising
background image

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

947

17

Function library

17.1

Function blocks

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

17.1.23.2 Deactivate motor potentiometer

When the motor potentiometer is deactivated by setting bInAct to TRUE, the nOut_a output signal

responds according to the function selected via Function.

[17-12] Example: Deactivation of the motor potentiometer when the Function = 1 has been selected

When the motor potentiometer is deactivated, nOut_a is reduced to 0 % with the deceleration time wTif.

If it is activated again, nOut_a is increased again to nLowLimit with the acceleration time wTir.

nOut_a

t

t

TRUE

FALSE

bUp

t

TRUE

FALSE

bDown

nHighLimit

nLowLimit

0

wTir

wTif

wTir

t

TRUE

FALSE

bInAct

wTif

wTif

0

1