Parameter | Name:

C00072 | SC: Tdn speed controller

Data type: UNSIGNED_16

Index: 24503

d

= 5FB7

h

Differential time constant Tdn of the speed controller for sensorless control for synchronous motors (

SLPSM

)

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

ms

3.00 0.00 ms

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00073 | Imax/M controller gain

Data type: UNSIGNED_16

Index: 24502

d

= 5FB6

h

Amplification factor Vp of certain controllers for different motor control modes
Setting range

(min. value | unit | max. value)

0.00

100.00

Subcodes

Lenze setting

Info

C00073/1

0.25

VFC

: Vp Imax controller

• After the motor to be used has been selected from the

motor catalogue, the suitable value can be entered

automatically.

C00073/2

1.25

SLVC

: Vp torque controller

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00074 | Reset time Imax/M controller

Data type: UNSIGNED_16

Index: 24501

d

= 5FB5

h

Reset time Ti of certain controllers for different motor control modes
Setting range

(min. value | unit | max. value)

0

ms

9990

Subcodes

Lenze setting

Info

C00074/1

65 ms

VFC

: Ti Imax controller

C00074/2

30 ms

SLVC

: Ti torque controller

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00075 | Vp current controller

Data type: UNSIGNED_16

Index: 24500

d

= 5FB4

h

Gain factor Vp of the current controller for certain inverter functions (parameter identification, flying restart circuit)

• After the motor to be used has been selected from the motor catalogue, the suitable value can be entered

automatically.

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

V/A

500.00 7.00 V/A

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT