9

Diagnostics & error management

9.9

Error messages of the operating system

466

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

PS08: Par. device invalid [xx.0144.00008]

PS09: Par. format invalid [xx.0144.00009]

PS10: Memory module binding invalid [xx.0144.00010]

dF14: SW-HW invalid [xx.0145.00014]

dF18: BU RCOM error [xx.0145.00024]

dF25: CU RCOM error [xx.0145.00025]

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The parameter set in the device is invalid.

• The error occurs while loading the parameter set.

• One code in the device is incorrect.

Consultation with Lenze required.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The code format is invalid.

• The error occurs while loading the parameter set.

Consultation with Lenze required.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Device personalisation is active: The binding ID of the

memory module does not comply with the binding ID of

the controller.

• Use memory module/controller with matching

binding IDs.

• Contact machine manufacturer.

Note:

It is not possible for Lenze to modify a replacement

device via special accesses in such a way that it

cooperates with a personalised memory module.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Device error

Consultation with Lenze required.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Device error

Consultation with Lenze required.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Device error

Consultation with Lenze required.