Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

701

15

Parameter reference

15.2

Parameter list | C00510

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00510

C00516

Parameter | Name:

C00510 | PW protection config MCI

Data type: UNSIGNED_16

Index: 24065

d

= 5E01

h

From version 15.00.00

Configuration of the password protection for parameter access via fieldbus interface ("MCI")

Individual password protection for single communication channels

Setting range

(min. hex value | max. hex value)

0x0000

0xFFFF

Value is bit-coded:

Info

Bit 0

Reserved

Bit 1 Parameter write protection

The fieldbus interface (MCI) cannot be used to write into

write/read parameters.

Bit 2 Parameter read protection

The fieldbus interface (MCI) cannot be used to read

write/read parameters.

Bit 3

Reserved

Bit 4

Reserved

Bit 5

Reserved

Bit 6

Reserved

Bit 7

Reserved

Bit 8

Reserved

Bit 9

Reserved

Bit 10

Reserved

Bit 11

Reserved

Bit 12

Reserved

Bit 13

Reserved

Bit 14

Reserved

Bit 15

Reserved

Subcodes

Lenze setting

Info

C00510/1

0x0006

PW protection config. MCI

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Parameter | Name:

C00516 | Checksums

Data type: UNSIGNED_32

Index: 24059

d

= 5DFB

h

This code is for device-internal use only and must not be written to by the user!