Diagnostics & error management

9.7

Maloperation of the drive

440

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.7

Maloperation of the drive

Maloperation

Cause

Remedy

Motor does not

rotate

DC-bus voltage is too low

• Red LED is blinking every 1 s

• Display in the keypad: LU

Check mains voltage

Controller is inhibited

• Green LED is blinking

• Display in the keypad:

Deactivate controller inhibit

• Note: Controller inhibit can be set via

several sources !

C00158

displays all active sources for

controller inhibit.

Automatic start is inhibited

(Bit 0 in

C00142

= 1)

LOW/HIGH edge at RFR

If required, correct starting condition with

C00142

DC-injection braking (DCB) is active

Deactivate DC injection brake

Mechanical motor brake is not released

Release mechanical motor brake manually or

electrically

Quick stop (QSP) is active

• Display in the keypad:

Deactivate quick stop

• Note: Quick stop can be set via several

sources!

C00159

displays all active sources for

quick stop.

Setpoint = 0

Select setpoint

JOG frequency = 0 at activated JOG setpoint Set JOG setpoint in

C00039/1...15

Fault active

Clear fault

With

C00006

= 4, "SLVC: Vector control" has

been set, but no motor parameter

identification has been carried out.

Execute automatic motor parameter

identification with the

C00002/23

device

command

Assignment of several mutually exclusive

functions with a signal source in

C00701

Correct configuration in

C00701

Motor rotates

irregularly

Motor cable is defective

Check motor cable

Maximum motor current in motor or

generator mode is set too low

Adjust settings to the application:

C00022:

Imax in motor mode

C00023

: Imax in generator mode

Motor is underexcited or overexcited

Check parameterisation:

C00006

: Motor control

C00015

: VFC: V/f base frequency

C00016

: VFC: Vmin boost

Rated motor data (stator resistance, speed,

current, frequency, voltage) and cos ϕ

and/or magnetising inductance is not

adapted to the motor data

Execute automatic motor parameter

identification with the

C00002/23

device

command

- or -

Adjust motor parameters manually:

C00084

: Motor stator resistance

C00087

: Rated motor speed

C00088

: Rated motor current

C00089

: Rated motor frequency

C00090

: Rated motor voltage

C00091

: Motor cosine phi

C00092

: Motor magnetising inductance

Motor windings are wired incorrectly

Reverse from star connection to delta

connection