8 mains phase failure monitoring, 9 maximum current monitoring, Mains phase failure monitoring – Lenze 8400 StateLine User Manual

Page 248: Maximum current monitoring, Ation, 5motor control (mctrl)

Advertising
background image

5

Motor control (MCTRL)

5.12

Monitoring

248

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.12.8

Mains phase failure monitoring

The drive controller has a simple mains-phase failure detection function with which a mains phase

failure can be detected under load.

• In the case of power-adapted machines, approx. 50 % of the rated motor power must be

exceeded so that a main-phase failure can be detected.

• If the mains phase failure monitoring is tripped:

• The error response set in

C00565

will be carried out (Lenze setting: "Warning").

• The "

Su02: One mains phase is missing

" error message will be entered into the logbook.

• The bMctrlMainsFault status output of the

LS_DeviceMonitor

system block will be set to

TRUE.

5.12.9

Maximum current monitoring

If the parameterised maximum current is reached, the response set in

C00609

is triggered (Lenze

setting: "0: No Reaction").
If the activated monitoring is tripped:

• The "

oC10: Maximum current reached

" error message is entered in the logbook.

Related topics:

Motor overcurrent monitoring

( 241)

Stop!

Under load, the mains input of a three-phase controller can be destroyed if the device is

only supplied by two phases (e.g. if a mains phase fails).

Note!

In the Lenze setting (

C00609

= "0: No Reaction"), the maximum current monitoring is not

activated!
If a Lenze motor is selected from the catalogue whose plant parameters are transferred

into the controller, the setting of the maximum current in

C00022

and

C00023

will

automatically be adapted to the selected motor.

Advertising