C00347 | can status heartbeat producer, C00349 | can setting - dip switch, C00347/1 – Lenze 8400 StateLine User Manual

Page 666: C00347/1...n, 15 parameter reference

Advertising
background image

15

Parameter reference

15.2

Parameter list | C00347

666

Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00347

C00349

Parameter | Name:

C00347 | CAN status HeartBeat producer

Data type: UNSIGNED_8

Index: 24228

d

= 5EA4

h

From version 03.00.00

Heartbeat protocol

Selection list

0 Boot-up
4 Stopped
5 Operational

127 Pre-Operat.
250 Failed
255 NoResponse

Subcodes

Info

C00347/1

Status node 1 ... 7

C00347/...
C00347/7

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00349 | CAN setting - DIP switch

Data type: UNSIGNED_16

Index: 24226

d

= 5EA2

h

DIP switch setting during last mains power-on

System bus "CAN on board"

Display area

(min. hex value | max. hex value)

0x0000

0xFFFF

Value is bit-coded:

Bit 0 Node address 1
Bit 1 Node address 2
Bit 2 Node address 4
Bit 3 Node address 8
Bit 4 Node address 16
Bit 5 Node address 32
Bit 6 Node address 64
Bit 7 Baud rate 1
Bit 8 Baud rate 2
Bit 9 Baud rate 4

Bit 10

Reserved

Bit 11

Reserved

Bit 12

Reserved

Bit 13

Reserved

Bit 14

Reserved

Bit 15 DIP switch at 24V-ON accepted

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT