Lenze · 8400 StateLine · Reference manual · DMS 12.0 EN · 06/2014 · TD05/TD14

77

4

Device control (DCTRL)

4.1

Device commands (C00002/x)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4.1.1

Load Lenze setting

The

C00002/1

= "1: On / start" device command resets the parameters to the Lenze setting which

are saved in the controller firmware.

• Can only be executed if the controller is inhibited; otherwise, the feedback

C00002/1

= "6: No

access - controller inhibit" will be returned.

• All parameter changes made since the last saving of the parameter set will get lost!
• This device command has an effect on the settings of the parameters of the operating system,

application and module.

How to load the Lenze setting:

1. If the controller is enabled, it must be inhibited, e.g. by executing the "Enable/Inhibit

controller" device command "(

C00002/16

= "0: Off / ready").

2. Execute the "Load Lenze setting" device command:

C00002/1

= "1: On / start"

The loading process may take a couple of seconds. After the device command has been

called,

C00002/1

returns dynamic status information ("Work in progress 20 %"  "Work in

progress 40 %"  "Work in progress 60 %", etc.).

Notes on execution time
The execution time of this device command usually is 2.5 s, independent of the communication

module used.
If - in addition to the device-internal time monitoring - a monitoring of the execution time is to be

implemented for this device command in a higher-level control, the monitoring time has to be 2 ...

3 times higher.